Product Details

Specifications

Items100kWh200kWh215kWh233kWh261kWh372kWh418kWh
SpecificationENNP-BES-100ENNP-BES-200ENNP-BES-215ENNP-BES-233ENNP-BES-261ENNP-BES-372ENNP-BES-418
Nominal Capacity100kWh200kWh215kWh233kWh261kWh372kWh418kWh
Nominal Voltage358.4V716.8V768V832V832V1331.2V1331.2V
Operating Voltage Range313.6V~408.8V627.2V~817.6V627.2V~817.6V728V~949V650V~949V1040V~1518.4V1040V~1518.4V
Battery Management SystemPassive BalancingPassive BalancingPassive BalancingPassive BalancingPassive BalancingPassive BalancingPassive Balancing
Battery TypeLFP-280LFP-280LFP-280LFP-280LFP-314LFP-280LFP-314
Battery Voltage Range2.8~3.65V2.8~3.65V2.8~3.65V2.8~3.65V2.8~3.65V2.8~3.65V2.8~3.65V
Standard Charge Rate0.5C0.5C0.5C0.5C0.5C0.5C0.5C
Cooling MethodAir CoolingAir CoolingLiquid CoolingLiquid CoolingLiquid CoolingLiquid CoolingLiquid Cooling
Battery Pack Grouping Method1P16S1P16S1P48S1P52S1P52S1P52S1P52S
Battery Cluster Connection Method1P112S1P224S1P240S1P260S1P260S1P416S1P416S
Protection LevelIP54IP54IP55IP55IP55IP55IP55
Noise<80dB (at 1m from the device)<80dB (at 1m from the device)<80dB (at 1m from the device)<80dB (at 1m from the device)<80dB (at 1 meter from the device)<80dB (at 1m from the device)<80dB (at 1 meter from the device)
Operating Altitude≤2000m≤2000m≤2000m≤2000m≤2000m≤2000m≤2000m
Operating Temperature﹣20~60℃-25 ℃~60℃﹣25 ℃~60℃-20~60℃-20~60℃-20~60℃-20~60℃
Relative Humidity≤95%RH, no condensation≤95%RH, no condensation≤95%RH, no condensation≤95%RH, no condensation≤95%RH, no condensation≤95%RH, no condensation≤95%RH, no condensation
Recommended SOC Usage Range5%~100%5%~100%5%~100%5%~100%5%~100%5%~100%5%~100%
Fire Fighting SystemPerfluorohexane (cluster level detection + cluster level fire fighting) + water fire fightingPerfluorohexane (cluster level detection + cluster level fire fighting) + water fire fightingPerfluorohexane (internal detection + cluster-level fire extinguishing) + cluster-level aerosol (optional) + water fire extinguishingPerfluorohexane (internal detection + cluster-level fire extinguishing) + cluster-level aerosol (optional) + water fire extinguishingPerfluorohexane (internal detection + cluster-level fire fighting) + cluster-level aerosol (optional) + water fire fightingPerfluorohexane PACK level fire extinguishing + water fire extinguishing + aerosolPerfluorohexane (internal detection + cluster-level fire extinguishing) + cluster-level aerosol (optional) + water fire extinguishing
Operating Temperature25±2℃25±2℃25±2℃25±2℃25±2℃25±2℃25±2℃
Communication MethodLAN/CAN/RS485LAN/CAN/RS485LAN/CAN/RS485LAN/CAN/RS485LAN/CAN/RS485LAN/CAN/RS485LAN/CAN/RS485
Size (L*W*H)1300mm*1450mm*2500mm 1300mm*1450mm*1950mm (substation)1300mm*1450mm*2500mm1400mm*1300mm*2100mm1400mm*1300mm*2100mm1400mm*1300mm*2250mm (double door) / 1000mm*1300mm*2400mm (single door)1400mm*1400mm*2500mm1450mm*1450mm*2600mm
Weight2T3T3T3T3T (double door) / 2.8T (single door)4T4T
Cell Circle Life≥6000次,@25℃,DOD95%,EOL80%≥6000次,@25℃,DOD95%,EOL80%≥6000次,@25℃,DOD95%,EOL80%≥6000次,@25℃,DOD95%,EOL80%≥6000次,@25℃,DOD95%,EOL80%≥6000次,@25℃,DOD95%,EOL80%≥6000次,@25℃,DOD95%,EOL80%


Leader in smart energy storage solutions

10003.png

Energy storage business

Wind, solar and storage integration + independent energy storage power station + industrial and commercial energy storage system, one-stop turnkey solution; large-scale delivery, cumulative global shipments exceeding 8GWh, full life cycle service guarantee

10005.png

Off-road machinery batteries

No. 1 in market share of aerial work platform battery systems · Top three in mining truck/loader battery industry;
Military-grade protection Industrial-grade reinforced design + IP68 protection + -40℃~85℃ full temperature range operation

10004.png

Battery System

Build a full life cycle strategy optimization process from battery parameter extraction, battery model establishment, BMS control strategy improvement, battery system product application, data platform analysis to hardware-in-the-loop verification to ensure safe and reliable operation of the product.

10006.png

BMS Product Advantages

With many years of experience in BMS research and development, we have established a rich battery operation database through detailed testing of various battery cells, and based on this, we have developed a high-precision SOX algorithm and a complete fault diagnosis and protection strategy.

message